Centrifugal Fan
SF160 Series
Applications
For high-demand commercial ventilation and air handling units requiring maximum airflow on standard 230 V AC power, the SF160D-E092B3-02 (EC, 230 V AC, 1700 m³/h, 180 W) delivers the highest air volume in the series with efficient electronically commutated operation. For medium-flow applications such as ducted air purification or heat recovery systems where balanced performance and lower power draw are priorities, the SF160D-E092A3-01 (EC, 230 V AC, 1200 m³/h, 165 W) provides a suitable energy-efficient solution. In North American installations with 115 V AC supply, the SF160D-E092B1-04 (EC, 115 V AC, 1450 m³/h, 220 W) is suitable for rooftop units and local exhaust systems where only low-voltage single-phase power is available. For high-static-pressure applications such as dense filter banks or long duct runs that demand greater torque and airflow, the SF160D-E092B3-42 (EC, 230 V AC, 1690 m³/h, 240 W) delivers the highest power output in the series for demanding industrial and commercial air movement.
| Model | Voltage | Power | Airflow | Noise | Speed Control | View Details |
|---|---|---|---|---|---|---|
| SF160D-E092A3-01 | 230 V AC | 165 W | 1200 m³/h | 52±2 dB(A) | 0-10V/PWM, 4-speed | View Details |
| SF160D-E092B1-04 | 115 V AC | 220 W | 1450 m³/h | 58 dB(A) | 0-10V/PWM, or 4-speed | View Details |
| SF160D-E092B3-02 | 230 V AC | 180 W | 1700 m³/h | 62±2 dB(A) | 0-10V/PWM, or 4-speed | View Details |
| SF160D-E092B3-42 | 230 V AC | 240 W | 1690 m³/h | 60±2 dB(A) | 3-speed, 4-speed | View Details |
FAQ
SF160D-E092B1-04
This SF160 series product offers EC motor + 4-speed speed control. Are these 4 speeds fixed, or can they be customized to 4 different rotation speeds according to customer needs?
This series supports up to 4 speeds (i.e., up to 4 speed lines), making it convenient to be compatible with the tap-winding speed control method used by AC asynchronous capacitor motors.
This SF160 series product provides 0-10V/PWM speed control. Is it an either/or choice, or are both compatible at the same time?
Both of these two stepless speed control methods, 0-10V and PWM, are compatible at the same time.
What are the advantages of an EC double inlet centrifugal blower compared with a single inlet blower?
The EC double inlet centrifugal blower draws in air from both sides, and when the motor is positioned in the center of the impeller it provides good impeller dynamic balance, greater airflow and higher static pressure. The EC single inlet blower draws in air from only one side, which makes its structure more compact and requires less installation space, so users should choose according to the specific application scenario.
SF160D-E092B3-02
This SF160 series product offers EC motor + 4-speed speed control. Are these 4 speeds fixed, or can they be customized to 4 different rotation speeds according to customer needs?
This series supports up to 4 speeds (i.e., up to 4 speed lines), making it convenient to be compatible with the tap-winding speed control method used by AC asynchronous capacitor motors.
This SF160 series product provides 0-10V/PWM speed control. Is it an either/or choice, or are both compatible at the same time?
Both 0-10V and PWM stepless speed control methods are compatible at the same time.
What are the advantages of an EC double inlet centrifugal blower compared with a single inlet blower?
The EC double inlet centrifugal blower delivers greater airflow and higher static pressure because it draws in air from both sides, and when the motor is positioned in the center of the impeller it provides good impeller dynamic balance. The EC single inlet blower draws in air from only one side, which makes its structure more compact and requires less installation space, so users should choose according to the specific application scenario.
SF160D-E092B3-42
Is this EC dual inlet extractor blower equipped with an EC motor with 4 speeds or 3 speeds? For the 4-speed version, are the speed values factory-set or user-adjustable?
This fan features an EC motor with 4 or 3 speed settings, and the speed value can be freely set by the user.
What equipment or industries is this EC dual inlet centrifugal blower mainly used in?
HVAC equipment is the most core application area for these fans, which are widely used in Air Handling Units (AHU), Fan Coil Units (FCU), Variable Air Volume (VAV) terminal devices, Primary Air Units (PAU), and Fan Filter Units (FFU).