Data Center Cooling Fans & EC Centrifugal Blowers

High-static-pressure EC centrifugal blowers for server racks, CRAC/AHU and DC power systems — 1050–25000 m³/h, up to 1500 Pa, with 0-10V/PWM temperature-driven & Modbus RTU(RS485) speed control.

Server racks, CRAC units and AHUs all share one requirement: the fan must push air through dense, high-resistance paths — filters, coils, cable trays and thousands of small component gaps. That is a static-pressure problem, not just an airflow problem, and it is exactly what SUNXFAN’s backward-curved EC centrifugal blowers are built to solve.

Why high static pressure matters in data centers

How to choose the right model

  1. Airflow (m³/h) — size for total kW of heat load (roughly 1 kW ≈ 170–200 m³/h).
  2. Static pressure (Pa) — the denser the rack and longer the duct, the higher the Pa you need.
  3. Power architecture — 115V/230V AC for standard racks; 310V/800 VDC for facilities running a central DC bus.
  4. Speed control — 0-10V/PWM for temperature-driven control, Modbus RTU for BMS integration.
  5. Redundancy — fan-wall arrays share load so a single failure never interrupts cooling.
ScenarioModelVoltageAirflowStatic PressurePowerNoise
High-static, 115VBC280A-E092D1-01115 V AC1540 m³/h550 Pa125 W71 dB(A)
High-static, 230VBC280A-E092D3-01230 V AC1540 m³/h715 Pa125 W71 dB(A)
1800 m³/h rack rowBC280A-E092E3-02230 V AC1800 m³/h715 Pa200 W77 dB(A)
Quiet 2000 m³/hBC280B-E092E3-02230 V AC2000 m³/h460 Pa200 W65 dB(A)
115V, 1950 m³/hBC310A-E092D1-01115 V AC1950 m³/h715 Pa160 W64 dB(A)
230V, 2100 m³/hBC310A-E092D3-01230 V AC2100 m³/h715 Pa160 W64 dB(A)
Max airflowBC310A-E092E3-02230 V AC2500 m³/h715 Pa240 W74 dB(A)
310V DC busDG200D-D092B0-01310 V DC1050 m³/h305 Pa120 W59 dB(A)
230V, 1300 m³/hDG200D-E092E3-01230 V AC1300 m³/h500 Pa190 W64 dB(A)

Bottom Line

For standard server racks on 230V AC, the BC280A-E092D3-01 (1540 m³/h, 715 Pa) offers the best balance of static pressure and efficiency. For high-density rows, step up to the BC310A-E092E3-02 (2500 m³/h, 715 Pa). If your facility runs a central DC bus, the DG200D-D092B0-01 (310 V DC) removes the onboard rectifier and shifts conversion heat out of the rack. Tell us your total heat load and power architecture, and we will confirm the exact fan and speed-control configuration.