Rack-mount fans: size by heat load, then check duct resistance

Start from the heat a cabinet generates and convert it to required airflow at the allowed temperature rise; dense racks with high flow resistance take rack-mount centrifugal blowers, open cabinet tops take axial fans.

The common mistake in cabinet cooling is sizing the fan by device count instead of by heat. The right sequence: total the heat inside the cabinet (kW) → set the allowed temperature rise (usually 10 K) → convert to airflow (m³/h) → then choose a rack-mount blower or an axial fan based on free space and flow resistance. Rack blowers use a wide, flat scroll to push air through densely packed equipment in 19-inch cabinets; axial fans are short and move large volumes, ideal for roof or door exhaust openings.

Selection points

  1. Airflow estimate: 1 kW of heat dissipation at a 10 K temperature rise needs roughly 300 m³/h; double the heat, double the airflow.
  2. Flow resistance: dust filters and densely packed equipment raise it sharply — step up to a higher-static-pressure rack blower.
  3. Mounting: do not short-circuit inlet and outlet; front-to-rear rack blowers need free space at both cabinet faces.
  4. Control and monitoring: EC models take 0-10V/PWM and alarm outputs, so fan speed can follow cabinet temperature and cut noise at night.

Model comparison

Model Airflow Max static pressure Power Noise Voltage
CF160-2000CFM-01 3400 m³/h 720 Pa 360W 66dB(A) 110-254 VAC
CF315A-E092E3-01 1750 m³/h 1001 Pa 220 W 66 dB(A) 230 VAC
CF250A-E092D1-01 1205 m³/h 1010 Pa 160 W 64dB(A) 120 VAC
CF146-650CFM-01 1100 m³/h 680 Pa 180 W 56dB(A) 110-254 VAC
CF200A-E092D3-01 1080 m³/h 905 Pa 160 W 63 dB(A) 230 VAC
CF160A-E072D1-01 820 m³/h 710 Pa 115 W 61dB(A) 120 VAC
CF150A-E072B3-01 720 m³/h 905 Pa 115 W 60 dB(A) 230 VAC
CF125A-E072A1-01 380 m³/h 810 Pa 85 W 60dB(A) 120 VAC

Specs are taken from each model's product page — full curves, dimension drawings and certificates live on the model pages. Models not listed can be browsed by series in the product catalogue.

Frequently asked questions

Should a 19-inch cabinet use a 1U or 2U fan?

Start from available height and heat load: 1U units fit telecom cabinets with moderate heat; high heat or high flow resistance calls for a 2U or dual-fan build with more airflow and static-pressure headroom.

How do I estimate the airflow a cabinet needs?

Use Q ≈ 3.1 × P / ΔT (Q in m³/h, P in W, ΔT in K). A 2 kW load at a 10 K rise needs about 620 m³/h — then add 20–30% margin for filter loading.

The cabinet fan is too loud — what now?

Slow it down first (EC models accept a direct 0-10V setback), then improve inlet/outlet clearance and opening ratio; swapping in a smaller fan usually gets louder because it has to spin faster.